What a vent does when the mains fails and the battery is flat
What each kind of opening rooflight does when the supply fails, why backup batteries quietly stop working, and the manual override that has to be reachable from the floor.
A mains-fed electric rooflight with no supply does not close, does not sense rain and does not report a fault. It stops where it is and waits, and if it was open when the power went, it is open until someone reaches it.
That is a dull answer until you put a date on it. The weather that takes out a supply in Dorset is the same south-westerly that drives rain across the harbour, and it arrives in the dark. This guide is about the design decisions that make that evening a non-event rather than a story.
The evening this page exists for
A large opening skylight over a kitchen, open a few inches because the room had been cooking all day. The supply drops at nine in the evening. The rain arrives twenty minutes later, on a wind that had been building since teatime. The unit is three and a half metres up.
Nothing in that sequence is unusual anywhere between Hamworthy and Highcliffe. What decides how it ends was settled months earlier, at survey: whether the unit has a backup module, whether that module still holds charge, and whether the manual override can be reached without a ladder in the dark.
What each type of unit actually does
| Unit | On loss of supply | What gets it closed |
|---|---|---|
| Mains-fed comfort rooflight, no backup | Stops in position. Rain and wind inputs dead with it | A manual override, or the return of the supply |
| Mains-fed with a backup module | Holds enough charge for a limited number of movements | The module, if it has been maintained and tested |
| Solar-powered skylight | Unaffected — it never used the house supply | Its own battery, provided the panel has been charging it |
| Escape rooflight | Must be openable by hand regardless | A person, by hand, with no electrical dependency at all |
| Certified AOV | Runs from the panel’s standby batteries and still operates | The panel, to the standby duration its fire specification set |
The row that matters to most households is the first one, because it is the default. A backup module is an option, and an option that is not taken is a sash that stays where it was.
Why the rain sensor dies with the motor
People reasonably assume the sensor is a safety device with its own life. It is not. The pad, the controller reading it and the drive it commands all sit on the same low-voltage supply, downstream of the same transformer. Cut the supply and the pad is still wet, still conductive and still entirely unheard.
This is the single most misunderstood thing about electric rooflights. The sensor is protection against inattention, not against power failure — those are different problems with different answers, and only one of them is solved by a sensor.
What a backup module really holds
A domestic backup module is a small sealed battery and a bit of switching that keeps the controller alive and gives the drive enough energy to move the sash a handful of times. It is not a house battery and it is not a UPS. Manufacturers specify it in movements, not hours, and that is the honest unit.
The question to ask, and the one not to
Ask: how many full close cycles does this module give from full charge, and what does it do first — some close the rooflight automatically on loss of supply, which is what most people actually want, while others simply keep the controls live so you can decide.
Do not ask how many hours it lasts. Standby time and working capacity are different numbers, and a module that keeps a light on the controller glowing for a day may have nothing left to move a heavy sash against a gasket.

Batteries do not fail loudly
A sealed battery loses capacity gradually, over years, without any outward sign. It sits on trickle charge, it never gets exercised, and the first honest test of it is the night it is needed. Heat shortens its life, deep cold reduces what it can deliver on the day, and a module in an unventilated loft gets both across a year.
Three to five years is the working assumption for domestic modules, less in a hot roof space. The failure is silent. Which is why the date matters more than the specification.
- Write the date on it. The month it was installed, on the module itself, in marker. Every later decision follows from that one label.
- Test it once a year. Isolate at the fused spur with the sash open a little, and watch what the unit does. That is the whole test.
- Test it in autumn. Before the weather that will need it, not in the spring when a failure is academic.
- Replace on age, not on failure. A module that failed its test has already been useless for an unknown length of time.
- Replace it after a long outage. A battery taken flat and left flat rarely comes back to what it was.
The override, and whether you can actually reach it
Every opening rooflight should have some way of being moved without power, and the forms vary more than people expect. What they have in common is that an override you cannot reach is not an override.
| Override type | How it works | The catch |
|---|---|---|
| Manual release on the drive | A lever or clip disengages the motor so the sash can be pushed shut | You have to get a hand to the actuator, which on a high ceiling means a tower |
| Crank or winder | A geared handle drives the mechanism directly | Only on units designed for it, and the handle must live somewhere findable |
| Pole operation | A hooked pole from floor level engages the sash or the release | Needs the clearance to swing a long pole, and the pole to still exist |
| Second manual rooflight | A separate hand-operated unit alongside the electric one | Costs another opening, and is the only fully reliable answer for escape |
We test the override at commissioning with the owner watching and, on a high-ceiling room, we do it from the floor rather than from our tower, because the demonstration is worthless if it only works from equipment we take away with us.
Solar units have the same problem wearing different clothes
A solar-powered skylight is the obvious answer to a retrofit into a finished ceiling, and it genuinely is immune to a power cut. It is not immune to a flat battery, and that is where the local detail bites.
Under the Branksome pines, solar is a poor bet. The canopy over Branksome Park and Canford Cliffs is protected, mature and not going anywhere. A roof-mounted panel under it sees a fraction of the light it was rated for, and across a Dorset winter — short days, low sun, wet needles on the panel — the battery never fully recovers between openings. The unit works beautifully in July and sulks from November.
Where a cable can still be run, a cable is the better answer in that zone, even though it means opening a route. Where it cannot, the compromise is a unit with a replaceable battery, a panel sited at the sunniest available position rather than the neatest, and an owner who knows to expect less of it in winter.

If yours is stuck open right now
- Protect the room first. Move what matters, get something absorbent under the opening. Water damage is cumulative and starts immediately.
- Check the spur, not the sash. If the rest of the house has power, the problem may be a tripped device or a blown fuse at the fused spur rather than a supply failure at all.
- Try the override from the floor. Pole or crank if the unit has one. Do not improvise a hook on a broom handle — a sash dropped onto a frame breaks a gasket seal that then leaks in every future storm.
- Do not go on the roof. A wet roof in wind, at night, to reach a rooflight is how people are seriously hurt. It can wait.
- Do not force a stalled drive. Pushing a sash against an engaged motor strips gearing and turns a power cut into a replacement.
- Note what it was doing. Position when it stopped, any controller lights, whether the sensor pad is wet. It shortens the repair visit considerably.
What we specify, and where
A backup module is standard on our quotations for any unit above a room where water would do real damage, and for any sash a person cannot reach from a step. On the spit it is standard regardless, because that is where the supply and the weather fail together most convincingly. Inland at Broadstone or Canford Heath, on a modest skylight over a hall with a reachable override, it is an option and we will tell you plainly that it is one.
Escape openings are the exception with no options in it. A rooflight serving as a means of escape from a loft room opens by hand, every time, with no power anywhere in the chain. We do not fit a motorised unit as an escape opening and call a battery module the answer to that, because a battery has a date on it and an escape route does not get to depend on one.
Our commissioning includes the override demonstration, the backup test and the date written on the module, and the settings go on the handover sheet. The installation carries a ten-year workmanship guarantee, plainly not insurance backed. To talk through what your unit should do on the night the lights go out, ring 01202 923272.
Related reading
Are electric rooflights noisy when they open?
No. A correctly installed unit makes a low hum for the twenty or thirty seconds it is moving and is…
Cable routing through a warm deck without breaching the vapour layer
The electrical side of getting power to an actuator is a settled matter, and it is set out on wiring…
Can a fixed rooflight be upgraded to an opening one?
Almost always this turns out to be a replacement rather than an upgrade, because a fixed rooflight has no hinge,…
Can a rooflight be set to close automatically at night?
Yes. A timed close is the most useful automation an opening rooflight can have, and unlike most of them it…
Can a smoke vent rooflight be used for everyday ventilation?
Technically, often yes — many certified automatic opening vents include a comfort ventilation mode, and it works. Practically, it is…
Can an electric rooflight be controlled from a phone?
Yes — either through a gateway that bridges the rooflight controller onto your home network, or through a manufacturer’s own…